DWYER Series AT-605 Differential Pressure Transmitter
RM 0.00
SKU: AT-605
Categories: BRAND, DIFFERENTIAL PRESSURE, Dwyer, Dwyer Instruments, PRESSURE TRANSMITTER, Pressure Transmitter
Tags: Dwyer AT-605, DWYER Series AT-605 Differential Pressure Transmitter
Description
Series AT-605 ATEX/IECEx Approved Magnehelic® Differential Pressure Indicating
Transmitter
The DWYER Series AT-605 Differential Pressure Transmitter provides for both visual monitoring and electronic control of very low differential pressure in hazardous locations. An easy-to-read dial gage is complimented by the two-wire, 4-20 mA control signal utilizing the time-proven Dwyer® Magnehelic® gage mechanical design and Series 600 transmitter technology. The two-wire design simplifies any 4-20 mA control loop powered by a 10-35 VDC supply. DWYER Series AT-605 Differential Pressure Transmitter Flameproof enclosures are available in aluminum and can include a glass window for viewing process pressure on the gage face.
Product Applications
- Monitor duct, room, or total building pressures
- Filter monitoring
- Local indication of clean room pressures with process signal sent to control room
- Hazardous area pressure measurement and transmitter
Features
- ATEX/IECEx housing provides all the capabilities and values of the Series 605 Magnehelic® transmitter in a flame and explosion proof enclosure
- Quick response to pressure changes means no delay in assessing critical situations
- Durable and rugged housing and high-quality components combined provide longservice life and minimized downtime
- High impact strength and high temperature rated for applications where hazardous environments exist
- Increased response time at low pressures with LD port configuration
Specifications
- GAGE SPECIFICATIONS
- Service: Air and non-combustible, compatible gases.
- Wetted Materials: Consult factory.
- Accuracy: See page reference on catalog page.
- Pressure Limits: See pressure limit chart on catalog page.
- Temperature Limits: 20 to 120°F (-6.67 to 48.9°C) (Note: Product temperature limits differ from case).
- Size: 4″ (101.6 mm) dial face.
- TRANSMITTER SPECIFICATIONS
- Accuracy: See page reference on catalog page. Includes linearity, hysteresis, repeatability.
- Compensated Temperature Range: 32 to 120°F (0 to 48.9°C).
- Thermal Effect: ±0.025% FS/°F (0.045% FS/°C).
- Stability: ±1% FS/year.
- Output Signal: 4-20 mA.
- Zero and Span Adjustments: Protected potentiometers on 605 face. Can access those by opening case. Allowed only in safe zone.
- Loop Resistance: DC: 0 to 1250 Ω max.
- Current Consumption: DC: 38 mA max.
- Electrical Connections: Screw terminal block.
- Mounting Orientation: Diaphragm in vertical position.
- Enclosure Rating: IP66 (IP65 for versions VS1/VS2/VL1).
- Housing Material: Aluminum.
- Finishing: Texture epoxy coat RAL7015.
- Process Connections: 1/8″ NPT female brass (SS optional).
- Electrical Connections: Two 1/2″ NPT female. Cable gland not included.
- Weight: 13.2 lb (6.0 kg).
- ATEX Certificate: INERIS 21ATEX0033X.
- IECEx Certificate: IECEx INE 21.0064X.
- Agency Approvals: ATEX Compliant: 0080 II 2G Ex db IIC T5, T6 Gb -60°C ≤Ta ≤+50°C (T6) -60°C ≤Ta ≤+60°C (T5) II 2D Ex tb IIIC T75 °C Db;
IECEx Compliant: Ex db IIC T5, T6 Gb -60°C ≤Ta ≤+50°C (T6) -60°C ≤Ta ≤+60°C (T5) Ex tb IIIC T75°C Db.