DWYER Series WE07 2-Piece Flanged Stainless Steel V-Ball Valve

RM 0.00

Description

Series WE07 2-Piece Flanged Stainless Steel V-Ball Valve

150# ANSI Flange, V-Ball, Electric or Pneumatic Actuators

The Series WE07 incorporates a V-port ball valve for impressive flow rates with minimal pressure drop. Quarter turn control ball valves are compact, lighter weight and much less expensive than comparable sized globe valves and segmented control valves. They also offer bubble tight shut off with zero leakage and can withstand high pressure drops. The 60° and 90° balls offer an equal percentage flow characteristic. W. E. Anderson’s V-port ball valves have been designed to offer maximum flow characteristics that are substantially higher than comparably sized globe valves. The natural flow pattern of ball valves increases flow rates and in many applications valves smaller than pipeline size can be used.
Actuators are direct mounted creating a compact assembly for tight spaces. Limit switches can be mounted directly to the valves allowing for remote position indication.

The Series WE07 can be configured with an electric or pneumatic actuator. Electric actuators are available in weatherproof or explosion-proof, a variety of supply voltages and Two-position modulating control.
Two-position actuators use the supply voltage to drive the valve open or close, while the modulating actuator accepts a 4 to 20 mA input for valve positioning. Actuators feature thermal overload protection and a permanently lubricated gear train.
The pneumatic double acting actuator uses an air supply to drive the valve open and closed. The actuator has two supply ports with one driving the valve open and the other driving the valve closed. Spring return pneumatic actuators use the air supply to open the valve and internally loaded springs return the valve to the closed position. Also available is the SV3 solenoid valve to electrically switch the air supply pressure between the air supply ports for opening and closing the valve. Actuators are constructed of anodized and epoxy coated aluminum for years of corrosion free service.

Product Applications

  • Gas or liquid flow control

 

Features

  • The 60° and 90° balls offer an equal percentage flow characteristic
  • Bubble tight shut off at high pressure drops
  • Limit switches can be mounted to manual valves for remote monitoring
  • Available with a variety of electric and pneumatic actuators

 

Specifications

 

VALVE

  • Service: Compatible liquids and gases.
  • Body: 2-piece.
  • Line Sizes: 1/2 to 3″.
  • End Connections: 150# ANSI flange.
  • Pressure Limits: 20″ Hg to 275 psi (-0.7 to 19 bar).
  • Wetted Materials: Body and ball: 316 SS (CF8M); Stem: 316 SS; Seat: RTFE/PTFE; Seal, Washer, and Packing: PTFE.
  • Temperature Limits: -20 to 392°F (-29 to 200°C).
  • Other Materials: O-ring: Fluoroelastomer; Handle: 304 SS; Washer: 301 SS; Stem Nut, Locking Device, Gland Ring: 304 SS; Handle Sleeve: PVC.
  • Agency Approvals: Meets the technical requirements of EU Directive 2011/65/ EU (RoHS II).

 

ACTUATORS

Pneumatic “DA” and “SR” Series

  • Type: DA series is double acting and SR series is spring return (rack and pinion).
  • Normal Supply Pressure: DA: 40 to 115 psi (2.7 to 7.9 bar); SR: 80 psi (5.5 bar).
  • Maximum Supply Pressure: 120 psi (8.6 bar).
  • Air Connections: DA01: 1/8″ female NPT; DA02 to DA04: 1/4″ female NPT; SR02 to SR06: 1/4″ female NPT.
  • Housing Material: Anodized aluminum body and epoxy coated aluminum end caps.
  • Temperature Limits: -40 to 176°F (-40 to 80°C).
  • Accessory Mounting: NAMUR standard.

 

Electric “TD” and “MD” Series

  • Power Requirements: 110 VAC, 220 VAC, 24 VAC or 24 VDC (MD models not available in 24 VDC).
  • Power Consumption: See instruction manual.
  • Cycle Time (per 90°): TD01: 4 s; MD01: 10 s; TD02 and MD02: 20 s; TD03 and MD03: 30 s.
  • Duty Rating: 85%.
  • Enclosure Rating: NEMA 4X (IP67).
  • Housing Material: Powder coated aluminum.
  • Temperature Limits: -22 to 140°F (-30 to 60°C).
  • Electrical Connection: 1/2″ female NPT.
  • Modulating Input: 4 to 20 mA.
  • Standard Features: Manual override, position indicator, and TD models come with two limit switches.

 

Electric “TI” and “MI” Series

  • Power Requirements: 110 VAC, 220 VAC, 24 VAC or 24 VDC.
  • Power Consumption: See instruction manual.
  • Cycle Time (per 90°): See instruction manual.
  • Duty Rating: See instruction manual.
  • Enclosure Rating: NEMA 7, designed to meet hazardous locations: Class I, Group C & D; Class II, Group E, F & G; Division I & II.
  • Housing Material: Powder coated aluminum.
  • Temperature Limits: -40 to 140°F (-40 to 60°C).
  • Electrical Connection: 1/2″ female NPT.
  • Modulating Input: 4 to 20 mA.
  • Standard Features: Position indicator and two limit switches.

 

Additional information